General information
Short description
Panel Feed-Through, Screw Connection
Long description
Panel Feed-Through, Screw Connection, M5, 600V, 85A
Category
Panel Feed-Through
Connection method
Screw connection
Pin demensions (Thickness x Width)(mm)
2.5x6.9
Material information
Insulation material group
I
Flame retardant rating , compliant with UL94
V0
Insulation resistance
≥500MΩ at DC 500V
Conductor material
COPPER ALLOY
Plating of conductor surface
Tin PLATED
Connection data-IEC
Rated voltage (III/3)(V)
400
Rated impulse voltage (III/3)(KV)
6
Conductor cross section solid. min (mm²)
0.5
Conductor cross section solid.max (mm²)
25
Conductor cross section stranded. min (mm²)
0.5
Conductor cross section stranded. max (mm²)
16
Conductor cross section flexible, with min ferrule without plastic sleeve (mm²)
0.5
Conductor cross section flexible, with max ferrule without plastic sleeve (mm²)
16
Conductor cross section flexible, with min ferrule with plastic sleeve (mm²)
0.5
Conductor cross section flexible, with max ferrule with plastic sleeve (mm²)
16
2 conductors with same cross section flexible, min twin ferrules with plastic sleeve (mm²)
0.5
2 conductors with same cross section flexible, max twin ferrules with plastic sleeve (mm²)
6
Slotted screwdriver size (Blade thickness x Width)(mm)
Hex socket 4
Philips screwdriver size
PZ2
Recommend tightening torque. min (N.m)
2
Recommend tightening torque. max (N.m)
2.9
Stripping Length (mm)
16~17
Connection data-UL
Rated voltage (UL/CUL Group B)(V)
300
Rated current (UL/CUL Group B)(A)
85
Rated voltage (UL/CUL Group D)(V)
300
Rated current (UL/CUL Group D)(A)
10
Min. solid wire connection (AWG) acc. to UL/CUL
22
Max. solid wire connection AWG acc. to UL/CUL
4
Min. stranded wire connection AWG acc. to UL/CUL
22
Max. stranded wire connection AWG acc. to UL/CUL
4
Environment & Safety
Back of the hand protection (YES or NO)
YES
Finger protection (YES or NO)
YES
Operating temperature. max (°C)
120
Operating temperature. min (°C)
-40
UL Recognized
Wire Range (Group B)(AWG)
22~4
Rated voltage (Group B)(V)
300
Rated current (Group B)(A)
85
Wire Range (Group D)(AWG)
22~4
Rated voltage (Group D)(V)
300
Rated current (Group D)(A)
10
CUL Recognized
Wire Range (Group B)(AWG)
22~4
Rated voltage (Group B)(V)
300
Rated current (Group B)(A)
85
Wire Ranget (Group D)(AWG)
22~4
Rated voltage (Group D)(V)
300
Rated current (Group D)(A)
10
The web catalog is for reference only. Dinkle remains the right of product modification and engineering change of the design. The final product is made according to engineering drawing.