General information
Short description
DIN rail terminal blocks, Feed through terminal blocks
Long description
DIN rail terminal blocks, Feed through terminal blocks, M6, 600V, 150A, Beige (default)
Category
Feed through terminal blocks
Connection method
Screw connection
Type of locking
Rail mounting
Material information
Insulation material group
I
Flame retardant rating , compliant with UL94
V0
Insulation resistance
≥500MΩ at DC 500V
Connection data-IEC
Rated voltage (III/3)(V)
1000
Rated impulse voltage (II/2)(KV)
8
Rated impulse voltage (III/2)(KV)
8
Rated impulse voltage (III/3)(KV)
8
Conductor cross section solid. min (mm²)
2.5
Conductor cross section solid.max (mm²)
50
Conductor cross section stranded. min (mm²)
2.5
Conductor cross section stranded. max (mm²)
50
Conductor cross section flexible, with min ferrule without plastic sleeve (mm²)
2.5
Conductor cross section flexible, with max ferrule without plastic sleeve (mm²)
35
Conductor cross section flexible, with min ferrule with plastic sleeve (mm²)
2.5
Conductor cross section flexible, with max ferrule with plastic sleeve (mm²)
35
2 conductors with same cross section, solid, min (mm²)
2.5
2 conductors with same cross section, solid, max (mm²)
16
2 conductors with same cross section, stranded, min (mm²)
2.5
2 conductors with same cross section, stranded, max (mm²)
10
2 conductors with same cross section flexible, with min ferrule without plastic sleeve (mm²)
2.5
2 conductors with same cross section flexible, with max ferrule without plastic sleeve (mm²)
10
2 conductors with same cross section flexible, min twin ferrules with plastic sleeve (mm²)
2.5
2 conductors with same cross section flexible, max twin ferrules with plastic sleeve (mm²)
10
Slotted screwdriver size (Blade thickness x Width)(mm)
1.0x5.5
Rated torque (N.m)
3.5~6.9
Recommend tightening torque. min (N.m)
3.5
Recommend tightening torque. max (N.m)
6.9
Stripping Length (mm)
16~18
End cover plate required
NO
Connection data-UL
Rated voltage (UL/CUL Group B)(V)
600
Rated current (UL/CUL Group B)(A)
150
Rated voltage (UL/CUL Group C)(V)
600
Rated current (UL/CUL Group C)(A)
150
Min. solid wire connection (AWG) acc. to UL/CUL
12
Max. solid wire connection AWG acc. to UL/CUL
1/0
Min. stranded wire connection AWG acc. to UL/CUL
12
Max. stranded wire connection AWG acc. to UL/CUL
1/0
Environment & Safety
Back of the hand protection (YES or NO)
YES
Finger protection (YES or NO)
YES
Operating temperature. max (°C)
120
Operating temperature. min (°C)
-40
UL Recognized
Wire Range (Group B)(AWG)
12~1/0
Rated voltage (Group B)(V)
600
Rated current (Group B)(A)
150
Wire Range (Group C)(AWG)
12~1/0
Rated voltage (Group C)(V)
600
Rated current (Group C)(A)
150
CUL Recognized
Wire Range (Group B)(AWG)
12~1/0
Rated voltage (Group B)(V)
600
Rated current (Group B)(A)
150
Wire Range (Group C)(AWG)
12~1/0
Rated voltage (Group C)(V)
600
Rated current (Group C)(A)
150
VDE Approval
DS35-XXP
Screw-on bridge
For DK35H. Beige color. Using UL94-V0 class of insulation material.
Add
CSC-35XXP
Insertion Bridge
For DK35H, DK35N. Beige color. Using UL94-V0 class of insulation material.
Add
TS-35
DIN-Rail
For DP / DK..N / DK.. / AK / DKB / DKU.. /DKM.. series. Material is iron. Length of 1000mm / 2000mm.
Add
TS-35/15
DIN-Rail
For DK / DK-PE series. Material is iron. Length of 1000mm / 2000mm.
Add
TS-35C
DIN rail end cap
For TS-35 rail. Black color. Using UL94-V2 class of insulation material.
Add
TM-R200
Continuous Flat Marking Labels
Add
TM50LW
Marking Label
For BEST APPLICATION: DP10, DP10-PE, DP10-TN, DP10-TN-PE, DKD10-P001, DPHD10-P001, DPH10 Series, AK10, AK10-PE, AK10-TN, AK10-TN-PE, DK10N, DK10N-PE, DK10N-TN, SS6N AVAILABLE APPLICATION: DP16, DP16-PE, DP16-TN, DP16-TN-PE, DPH16 Series, AK16, AK16-PE, AK16-TN, AK35, DK10-PE, DK16N, DK16N-PE, DK16H, DK16-PE, DK16T, DK35N, DK35H, DK35H-PE, DK50, DK50-PE, DK95, DK95-PE, DK150, DK240, DKM Series White color. Using UL94-V0 class of insulation material.
Add
DKNSPS-004
Partition Plate
For DK16N, DK35N, DK35H. Beige color. Using UL94-V0 class of insulation material.
Add
The web catalog is for reference only. Dinkle remains the right of product modification and engineering change of the design. The final product is made according to engineering drawing.