General information
Short description
DIN rail terminal blocks, Grounding terminal blocks
Long description
DIN rail terminal blocks, Grounding terminal blocks, Green-Yellow (default)
Category
Grounding terminal blocks
Color
Green-Yellow (default)
Connection method
Screw connection
Type of locking
Rail mounting
Material information
Insulation material group
I
Flame retardant rating , compliant with UL94
V0
Insulation resistance
≥500MΩ at DC 500V
Connection data-IEC
Rated impulse voltage (II/2)(KV)
8
Rated impulse voltage (III/2)(KV)
8
Rated impulse voltage (III/3)(KV)
8
Conductor cross section solid. min (mm²)
0.14
Conductor cross section solid.max (mm²)
6
Conductor cross section stranded. min (mm²)
0.14
Conductor cross section stranded. max (mm²)
4
Conductor cross section flexible, with min ferrule without plastic sleeve (mm²)
0.25
Conductor cross section flexible, with max ferrule without plastic sleeve (mm²)
4
Conductor cross section flexible, with min ferrule with plastic sleeve (mm²)
0.25
Conductor cross section flexible, with max ferrule with plastic sleeve (mm²)
4
2 conductors with same cross section, solid, max (mm²)
1.5
2 conductors with same cross section, stranded, max (mm²)
1.5
2 conductors with same cross section flexible, with min ferrule without plastic sleeve (mm²)
0.25
2 conductors with same cross section flexible, with max ferrule without plastic sleeve (mm²)
1
2 conductors with same cross section flexible, min twin ferrules with plastic sleeve (mm²)
0.5
2 conductors with same cross section flexible, max twin ferrules with plastic sleeve (mm²)
1.5
Slotted screwdriver size (Blade thickness x Width)(mm)
0.6x3.5
Philips screwdriver size
PH1
Stripping Length (mm)
9~11
End cover plate required
YES
Grounding connections
YES
Connection data-UL
Min. solid wire connection (AWG) acc. to UL/CUL
28
Max. solid wire connection AWG acc. to UL/CUL
10
Min. stranded wire connection AWG acc. to UL/CUL
28
Max. stranded wire connection AWG acc. to UL/CUL
10
Environment & Safety
Back of the hand protection (YES or NO)
YES
Finger protection (YES or NO)
YES
Operating temperature. max (°C)
120
Operating temperature. min (°C)
-40
VDE Approval
TM48LW
Marking Label
For BEST APPLICATION: DP4N, DP4N-PE, DP4N-TN, DP4N-TN-PE, DP4N-TR, DP4N-TR-PE, DP4N-3L-SPE, AK4, AK4-PE, AK4-TN, AK4-TN-PE, AK4-TR, AK4-TR-PE, DK4N Series, DKK4N Series. AVAILABLE APPLICATION: DK4-PE White color. Using UL94-V0 class of insulation material.
Add
DK2.5NC-TR-PE
End Cover
For DK2.5N-TR-PE/DK4N-TR-PE Green (default) Using UL94-V0 class of insulation material.
Add
TS-35
DIN-Rail
For DP / DK..N / DK.. / AK / DKB / DKU.. /DKM.. series. Material is iron. Length of 1000mm / 2000mm.
Add
The web catalog is for reference only. Dinkle remains the right of product modification and engineering change of the design. The final product is made according to engineering drawing.