Short description
DIN Rail terminal blocks, Screw connection
Long description
Feed-Through single level, Screw Connection, Width:10.5mm, M4, 600V, 30A
Category
Rail mounting terminal blocks
Connection method
Screw connection
Type of locking
Rail mounting
Material information
Insulation material group
IIIa
Flame retardant rating , compliant with UL94
V2
Insulation resistance
≥1000MΩ at DC 500V
Conductor material
Copper Alloy
Plating of conductor surface
Tin PLATED
Connection data-IEC
Rated voltage (III/3)(V)
630
Rated impulse voltage (II/2)(KV)
8
Rated impulse voltage (III/2)(KV)
8
Rated impulse voltage (III/3)(KV)
8
Conductor cross section solid. min (mm²)
0.34
Conductor cross section solid.max (mm²)
4
Conductor cross section stranded. min (mm²)
0.34
Conductor cross section stranded. max (mm²)
4
2 conductors with same cross section, solid, max (mm²)
4
2 conductors with same cross section, stranded, max (mm²)
4
Philips screwdriver size
PH2
Rated torque (N.m)
1.2~1.5
Recommend tightening torque. min (N.m)
1.2
Recommend tightening torque. max (N.m)
1.5
Stripping Length (mm)
The stripping length depends on the specification provided by the cablelug manufacturer.
Mounting rail
TS-35N、TS-35/15N
End cover plate required
YES
Connection data-UL
Rated voltage (UL/CUL Group B)(V)
600
Rated current (UL/CUL Group B)(A)
30
Rated voltage (UL/CUL Group C)(V)
600
Rated current (UL/CUL Group C)(A)
30
Min. solid wire connection (AWG) acc. to UL/CUL
22
Max. solid wire connection AWG acc. to UL/CUL
10
Min. stranded wire connection AWG acc. to UL/CUL
22
Max. stranded wire connection AWG acc. to UL/CUL
10
Environment & Safety
Back of the hand protection (YES or NO)
YES
Finger protection (YES or NO)
NO
Operating temperature. max (°C)
125
Operating temperature. min (°C)
-40
UL Recognized
Wire Range (Group B)(AWG)
22~10
Rated voltage (Group B)(V)
600
Rated current (Group B)(A)
30
Wire Range (Group C)(AWG)
22~10
Rated voltage (Group C)(V)
600
Rated current (Group C)(A)
30
Wire Range (Group D)(AWG)
22~10
Rated voltage (Group D)(V)
600
Rated current (Group D)(A)
30
CUL Recognized
Wire Range (Group B)(AWG)
22~10
Rated voltage (Group B)(V)
600
Rated current (Group B)(A)
30
Wire Range (Group C)(AWG)
22~10
Rated voltage (Group C)(V)
600
Rated current (Group C)(A)
30
Wire Ranget (Group D)(AWG)
22~10
Rated voltage (Group D)(V)
600
Rated current (Group D)(A)
30
TS-35/15
DIN-Rail
For DK / DK-PE series. Material is iron. Length of 1000mm / 2000mm.
Add
TS-35
DIN-Rail
For DP / DK..N / DK.. / AK / DKB / DKU.. /DKM.. series. Material is iron. Length of 1000mm / 2000mm.
Add
DKB30NE
End Cover
Add
TM-R100
Continuous Flat Marking Labels
Add
CSK11-30XX-A
Insertion bridge
For DKU30, DKUP30-XXPK, DKB30N, DKB30N-XXPCK. Material is copper alloy then tin-plated on surface.
Add
The web catalog is for reference only. Dinkle remains the right of product modification and engineering change of the design. The final product is made according to engineering drawing.